What size inverter do I need?
A worked method for choosing inverter power, with examples you can adapt.
Step 1: list what will run at the same time
Write down every appliance that could be on at once and its running power in watts (on the nameplate or in the manual). If only amps are given, multiply by the AC voltage: a 5A appliance on 120V draws about 600W.
Step 2: add a safety margin
Add the running watts together and multiply by 1.25. Running an inverter continuously at 100% shortens component life and leaves no room for an extra load.
Step 3: check start-up surge
Motors draw two to three times their running power for a fraction of a second when they start, and compressors (fridges, air conditioners) can draw more. The inverter's peak or surge rating must cover the largest motor's start-up power plus everything else that is already running. On our LCD models the peak rating is printed next to the rated power: the 1,500W unit, for example, handles 3,000W peak.
Step 4: choose battery voltage
DC current equals inverter power divided by battery voltage, divided by efficiency. A 3,000W load on 12V draws about 3,000 / 12 / 0.9 ≈ 280A; on 48V it is about 70A. High current needs heavy cables, large fuses and a battery that can deliver it. See 12V vs 24V vs 48V.
Worked examples
| Scenario | Loads | Running total | Suggested inverter |
|---|---|---|---|
| Camper van | Fridge 100W, laptop 65W, lights 40W, kettle 1,000W | ~1,200W | 1,500W, 12V |
| Motorhome | Fridge 150W, microwave 1,200W, TV 100W, coffee machine 900W (not together with microwave) | ~1,450W | 2,000W, 12V or 24V |
| Home backup (essentials) | Fridge 200W, freezer 150W, router 20W, lights 100W, furnace blower 500W | ~970W, surge ~2,000W | 2,000–3,000W, 24V or 48V |
| Job site | Circular saw 1,800W, drill charger 200W, lights 100W | ~2,100W, surge ~4,000W | 3,000W, 24V |
| Cabin with air conditioner | AC 1,200W, fridge 150W, well pump 750W, lights 100W | ~2,200W, surge ~5,000W | 5,000–6,000W, 48V |
Step 5: size the battery
Multiply average load by hours of runtime and divide by about 0.9 for inverter losses. For lithium batteries you can use most of the rated capacity; for lead-acid, plan on using about half to protect battery life.
Not sure? Send us your appliance list through the contact form and our engineers will recommend an inverter and battery configuration.