ST series rack inverter, 1000–6000VA
2U, built-in transfer switch
Ask for price and datasheetThe ST series delivers pure sine wave AC from a 2U, 19-inch rack chassis. It runs from 24V or 48V telecom batteries or from 110V, 220V and 250V DC plant systems, and its built-in automatic transfer switch keeps critical loads powered when either source fails.
Models run from 1,000VA to 6,000VA with 220–240V output, or 1,000VA to 4,000VA with 100–120V output. Versions with a 48V charging module are also available.

482 mm wide and 88.8 mm high; depth 272–451 mm depending on model.
Transfers between inverter and mains in 8–10 ms.
Pure sine wave, THD 3% or less on 120V models and 5% or less on 230V models.
Surge power is twice the continuous rating.
Status and settings on the front LCD; RS485 for connection to a PC.
−20 to 59°C, full performance to 50°C; audible noise under 55 dB.
| Model | Rating | Continuous power | Surge power | AC output versions |
|---|---|---|---|---|
| ST1000 | 1,000VA | 800W | 1,600W | 220/230/240V or 100/110/120V |
| ST2000 | 2,000VA | 1,600W | 3,200W | 220/230/240V or 100/110/120V |
| ST3000 | 3,000VA | 2,400W | 4,800W | 220/230/240V or 100/110/120V |
| ST4000 | 4,000VA | 3,200W | 6,400W | 220/230/240V or 100/110/120V |
| ST5000 | 5,000VA | 4,000W | 8,000W | 220/230/240V |
| ST6000 | 6,000VA | 4,800W | 9,600W | 220/230/240V |
| DC series | Nominal input | Operating range | Ratings (230V output) |
|---|---|---|---|
| 24V series | 24V DC | 20–30V | 1,000–3,000VA |
| 48V series | 48V DC | 44–58V | 1,000–6,000VA |
| 110V series | 110V DC | 90–145V | 1,000–6,000VA |
| 220V series | 220V DC | 180–270V | 1,000–6,000VA |
| 250V series | 250V DC | 200–295V | 1,000–6,000VA |
Models with 100–120V output are available up to 4,000VA.
| Item | Specification |
|---|---|
| Efficiency | Up to 91% (120V models), 90% (230V models) |
| Output frequency | 50/60Hz ±0.1Hz |
| Transfer time | 8 ms inverter to mains, 10 ms mains to inverter |
| Protection | Reverse polarity; electronic current limiting at overload and short circuit |
| Cooling | Forced air |
| Altitude | Up to 1,500 m |
| Interface | RS485 |
| Dimensions (W×D×H) | 482 × 272–451 × 88.8 mm |
| Weight | 5.3–9.5 kg |
| Standards | CE, RoHS; EN 60950-1 safety; EN 300 386 EMC |

2U, built-in transfer switch
Ask for price and datasheet
Inverter and battery charger
Ask for price and datasheet
For power-plant DC systems
Ask for price and datasheetTelecom base stations, fibre nodes and data rooms already run on 48V DC battery plants. A rack inverter lets that battery supply AC loads (routers, fans, monitoring PCs) without a separate UPS, and the built-in transfer switch uses mains power when it is available. In substations and power plants, 110V, 220V or 250V DC batteries back up protection and control systems; our high-voltage DC models supply AC for SCADA computers and lighting from the same source.
DC bus voltage: match the series to your battery plant; the operating ranges are in the table above. Capacity: add up the AC loads in watts and choose a model whose continuous power (80% of its VA rating) covers them with headroom. Charging: choose a 48V charging-module version if the unit must also maintain the battery. See our telecom and industrial page for typical configurations.
ST models are 2U (88.8 mm) high and 482 mm wide for standard 19-inch racks. Depth is 272–451 mm depending on model and DC series; the manual lists each one.
Yes. Besides 24V and 48V, the ST series comes in 110V (90–145V), 220V (180–270V) and 250V (200–295V) DC input versions.
The built-in automatic transfer switch moves the load to inverter power in about 10 ms, and back to mains in about 8 ms.
Yes, versions with a 48V charging module are available.
Tell us the model, input and output voltage, quantity and destination. An engineer will reply with pricing and lead time.